Small Valve-Regulated Lead Acid Batteries

HZ Series

Small Valve Regulated Type

High-rate discharge small valve regulated lead-acid batteries featuring high energy density and space-saving design.

The HZ Series is a line of high-rate discharge small valve regulated lead-acid batteries that achieve high energy density and space-saving installation.

※This product is manufactured by CSB Energy Technology Co., Ltd., a group company of Energywith. (Country of origin: Vietnam)

Features

  • Suitable not only for standby use but also for cycle use.
  • Expected service life for standby use is 5 years at 25°C with 0.25CA discharge.
  • Expected service life for cycle use is 200 cycles at 100% depth of discharge (DOD) and 25°C.

※“Expected service life” refers to the period converted to constant 25°C operating conditions based on results from high-temperature accelerated life testing. This value is an estimate under specified conditions and does not guarantee battery life under all operating conditions.

Main Applications

  • UPS
  • CATV
  • Emergency lighting
  • Disaster prevention equipment
  • Disaster prevention and security systems

Specifications

ModelUnitHZ7.2-12HZ12-12
Nominal voltage (Note 1)V1212
Capacity (Note 3)
25℃
20-hour rate (0.05CA)
F.V. (Note 2) = 1.75V/cell
Ah7.212.0
10-hour rate (0.09CA)
F.V. = 1.75V/cell
Ah6.310.6
5-hour rate (0.17CA)
F.V. = 1.75V/cell
Ah6.110.0
3-hour rate (0.25CA)
F.V. = 1.70V/cell
Ah5.49.0
1-hour rate (0.60CA)
F.V. = 1.60V/cell
Ah4.37.2
10-minute rate (3CA)
F.V. = 1.30V/cell
Ah3.66.0
DimensionsOverall heightmm98.6±1100.3±1.5
Case heightmm94.3±194.1±1
Lengthmm150.9±2151±2
Widthmm64.8±198±1
Weightapprox. kg2.73.9
Terminal typeF2F2
Flame retardancy of container materialUL 94V-0
Internal resistance (Note 4) (25°C)approx. mΩ1715
Current-carrying capacity (5 seconds)A108180
Constant voltage chargingStandby use charging voltageV13.65(25℃)
Cycle use charging voltageV14.70(25℃)
Maximum charging currentA2.163.6
Operating temperature range (Note 5)Charging-15~40℃
Discharging-15~50℃
Storage-15~40℃
UL certification○:File No. MH14533
Certified battery equipment

Note 1: The nominal voltage of lead-acid batteries is 2V per cell. These batteries consist of six cells connected in series inside the battery.
Note 2: F.V. is an abbreviation for Final Voltage, indicating the discharge end voltage.
Note 3: “C” in this table indicates the 20-hour rate capacity (C20). For example, for model HZ7.2-12, C (C20) = 7.2.
Note 4: Measured value (for reference) obtained using a Battery HiTester®.
Note 5: During operation (charging and discharging), it is recommended that the battery temperature be maintained between 5°C and 35°C. For storage, keep the battery at 30°C or lower whenever possible.

Dimension Notation

Product Photos

Top: HZ7.2-12
Bottom: HZ12-12

Terminal shape