DC Power Supply Systems

DC Power Supply System (for Telecommunications Facilities)

DC Power Supply System

Backup power source for critical facilities where power outages are not permitted, including telecommunications facilities, power receiving and distribution equipment for transportation systems, emergency lighting systems in buildings, and water treatment facilities.

For Telecommunications Facilities

24V Systems / 48V Systems

  • Cubicle-type battery equipment compliant with the Fire Prevention Ordinance
  • Sine-wave input switching method reduces input power distortion and minimizes harmonic interference to the power supply side
  • Widely used as a power source for telecommunications equipment and control devices
  • Highly reliable and maintainable power supply adopting an n+1 configuration

Specifications

Item24 V System        48 V System        Remarks
EnvironmentAmbient temperature−10 to 40°CJIS C 4402
Relative humidity25–85% (non-condensing)
Altitude≤ 1,000 m
TypeRated operationContinuous
Control methodTransistor pulse-width control            
Cooling methodNatural cooling or forced air cooling
AC InputNumber of phasesSingle-phase or three-phase
Rated input voltage100V200V100V200V
Voltage fluctuation range180~220V180~220V
Power factor≥80% (single-phase), ≥90% (three-phase)Depends on model
Rated frequency50/60 Hz (common)
Frequency fluctuation range50Hz±5% /60Hz±5%
DC Output (Unit)  Voltage26.8(29.0)V53.5(55.8)VSee Note 2
Voltage adjustment range±0.5V or more±1.0V or more    
Constant voltage accuracySinglethree-phaseSinglethree-phase
≤2.0%   ≤2.0%   
Rated CurrentInput Voltage 100 or 200V Input Voltage 200VInput Voltage 100 or 200V Input Voltage 200V
25、50A25、50、100A10、20、30、40、50A
Current fluctuation range0~100%≤2V/cell
Maximum sag current≤105%   At rated input/output
DC Output
(Device Load Side) 
Efficiency70% or higher
Rated Currentn Method10 or 50 or 100A × nn is the number of units
n+1 configuration10 or 50 or 100A × n+1
Compensation device
Load voltage
Load voltage Range24V ±10% or less48V ±10% or less
Rated CurrentSame as rated current
Current Variation Range10 to 100%
Ripple Voltage300mVp-p or lessWhen battery is connected
Evaluation Noise5mV or lessWhen battery is connected

Note 1: When considering HS or CS types instead of MSE-type valve regulated stationary lead-acid batteries, please contact us.
Note 2: The above values indicate 12-cell and 24-cell configurations. DC output voltages for 13-cell and 25-cell configurations are shown in parentheses.

Applicable Standards

  • Japanese Industrial Standards (JIS)
  • Electrotechnical Committee Standards (JEC)
  • Japan Electrical Manufacturers’ Association Standards (JEM)
  • Storage Battery Association Standards (SBA)
  • For battery equipment of 4,800Ah per cell or greater subject to the Fire Prevention Ordinance, compliant cubicles will be used.
  • Please contact us if compliance with other standards is required.

13.8V Systems

ItemsRated Specifications and Performance
MethodRectification methodTransistor pulse width modulation
Cooling methodNatural cooling
Rated operationContinuous operation
AC InputNumber of phasesSingle-phase 2-wire
Rated voltage100V
Voltage fluctuation range±10% of rated voltage
Rated frequency50/60Hz
Frequency fluctuation range±5% of rated frequency
DC OutputCharging method Float charging (for MSE type)
Rated voltageDetermined by battery type and quantity
Voltage adjustment range±3% or more of float voltage
Constant voltage accuracyWithin ±2%
Current fluctuation range0–100%
Maximum current droop≤120% of rated current
Ripple voltage≤20mV p-p (with battery connected, resistive load)
Evaluated noise≤2mV (with battery connected, resistive load)
Load voltage compensationWithin ±10% of rated value for load variations of 10–100%

DC Power Supply Systems: Applications and Series