DC Power Supply Systems

DC Power Supply System (for Power Facilities) / Lead-Acid Battery Equipped Type

DC Power Supply System

Backup power source for critical facilities where power outages are not permitted, including telecommunications facilities, power receiving and distribution equipment for transportation systems, emergency lighting systems in buildings, and water treatment facilities.

A0, AX, SX Series LA, LS Series (Front-panel LCD type)

Standard Specifications

ItemsA0(LA)SeriesAX SeriesSX(LS) Series
System configurationRectification methodSingle-phase full-wave (hybrid bridge method) / Three-phase full-wave (pure bridge method)Single-phase full-wave / Three-phase full-wave
Cooling methodNatural cooling or forced air coolingNatural cooling or forced air cooling
Rated operationContinuousContinuous
AC InputNumber of phasesSingle-phase 2-wire or three-phase 3-wireSingle-phase 2-wire or three-phase 3-wire
Rated voltageSingle-phase 100、105、110、200、210、220V
Three-phase 200、210、220、400、415、420、440V
Single-phase 100、105、110、200、210、220V
Three-phase 200、210、220、400、415、420、440V
Voltage fluctuation range±10%±10%
Rated frequency50 or 60 Hz50 or 60 Hz
Input power factorSingle-phase: 60% or higher
Three-phase: 70% or higher
97% or higher (excluding 24V systems)
DC OutputDC OutputFloat / equalizing charge switching method
(excluding combinations with valve regulated lead-acid batteries)
Float charging method
(excluding combinations with valve regulated lead-acid batteries)
Rated voltage24 / 48 / 100V systems ※1
Voltage adjustment range±3% or more of float voltage±3% or more of float voltage
Constant voltage accuracy±2% or less (excluding 12V and 24V systems)±2% or less (excluding 24V systems)
Output currentSingle-phase input10、15、20、30、40A10~50A
Three-phase input10、15、20、30、40、50、75、100、150A ※210~300A ※2
Current fluctuation range0~100%0~100%
Maximum current droop120% or less of rated current105% or less of rated current
General ConditionsAmbient temperature-10~40℃-10~40℃
Relative humidity  25 to 85% (non-condensing)  25 to 85% (non-condensing)  
Installation locationIndoor locations at altitudes of 1,000 m or less, with minimal presence of harmful gases, salt, and dustIndoor locations at altitudes of 1,000 m or less, with minimal presence of harmful gases, salt, and dust

※1 For higher voltage requirements, please contact us.
※2 For higher current requirements, please contact us.

Applicable Standards

  • Japanese Industrial Standards (JIS)
  • Electrotechnical Committee Standards (JEC)
  • Japan Electrical Manufacturers’ Association Standards (JEM)
  • Storage Battery Association Standards (SBA)
  • Fire Prevention Ordinance (example): Standards under Article 13
  • Fire and Disaster Management Agency Notification No. 2 (1973): Standards for storage battery equipment
  • Please contact us if compliance with other standards is required.

Standard Cubicle (Battery Panel)

Lead-acid battery modelStandard dimensions of battery panelWeightApplicable series
MSE・MSJHSEHSCSWidth W (mm) × Depth D (mm) × Height 2300 mm or 1900 mm (excluding base)(kg)A0AXSX
50-12,100-630-12,40-12,50-12,60-6,80-6,100-615-6,30-6600X900230
150,20030,40,50,60-615,30,45-6700X900250
Jun-80Jun-60800X900290
30060,8045,60900X900300
150,200,250130.171000X900320
400100-6,120-6Jun-90(600X2)X900450
500100,12090(700X2)X900490
600 (300X2)300,400210,250,290(800X2)X900530
700(500+200)(900X2)X900590
500,600400(900X3)X900870
800(500+300)(900X2)X1000620
700.800,900500,600(900X3)X1000930
1000(900X2)X1200700
1500(800X4)X1200*11280
10,001,200700,800,900(1000X5)X900*11500

*1: For front-and-rear maintenance (doors on both sides). For front-side maintenance only: (900 × 4) × 900 × 2300, weight 1500 kg.
*2: For front-and-rear maintenance (doors on both sides). For front-side maintenance only: (900 × 8) × 900 × 2300, weight 2400 kg.

AE Series

  • Dropper-less design for reduced losses and improved reliability
  • Float charging voltage of 107V with a 48-cell battery configuration
  • Compact design enabling space saving
ItemAE Series
MethodRectification methodThree-phase full-wave (pure bridge method)
Cooling methodNatural cooling
Rated operation100% continuous
AC InputNumber of phasesThree-phase 3-wire (single-phase 2-wire available as an option)
Rated voltage200V system (400V system available as an option)
Voltage fluctuation range±10%
Rated frequency50 or 60 Hz
Frequency fluctuation range±5%
Power factor70% or higher (at maximum rated output load, measured by instrument)
Input capacity3, 5, 7, 9, 13, 17 kVA or less
DC OutputCharging methodFloat charging
Rated voltage107V
Voltage adjustment range103~107V
Constant voltage accuracy±2% or less
Rated current10、20、30、50、75、100A
Current fluctuation range0~100%
Maximum current droop120% or less of rated current
Ripple factor10% or less (r.m.s)
Efficiency80% or higher (at rated input/output)
General ConditionsAmbient temperature-10~40℃(JIS C 4402)
Relative humidity25–85% (non-condensing)
Installation locationIndoor locations at altitudes of 1,000 m or less, with minimal presence of harmful gases, salt, and dust